-  Max. five micromodules, with peripheral module Part No. 772477, up to five esserbus analog loop modules (system supports up to 635 digital loop addresses in total)
 
    -  Max. seven micromodules, with extension module Part No. 772476, up to seven esserbus analog loop modules (system supports up to 889 digital loop addresses in total)
 
    -  Short circuit and open circuit tolerant loop operation
 
    -  Loop installation with I-Y(ST)Y 0.8 mm cable for a maximum length of 3.5 km
 
    -  Up to 127 esserbus devices (fire detectors and/or manual call points)/detector zones per loop
 
    -  Up to 32 esserbus transponders per loop/operation of wireless components (see chapter 10)
 
    -  Operation types TM and PM as per DIN VDE 0833 - 2 to avoid unwanted alarms being triggered
 
    -  Fire brigade operating panel and transmission interface on the peripheral module
 
    -  Three common relays, freely programmable, monitored, floating for up to 30 V DC/1A (on the peripheral module)
 
    -  TTY or RS 485 or RS 232 interface
 
    -  Integration in the short circuit and open circuit resistant essernet network with up to 31 fire detection panels depends on transmission rate
 
    -  Connection to graphical supervisor WINMAG via serial essernet interface (SEI)
 
    -  Operating panel with alphanumerical display 
 
    -  Large LCD display with 8 rows x 40 characters
 
    -  Event memory for up to 10,000 events
 
    -  All Systems 8000 micromodules are compatible 
 
    -  Printer interface for internal printer 
 
    -  Two batteries with monitoring circuit
 
    -  Monitored input for external power supply unit
 
Additional features for powered loop
    -  Max. 6 analog powered loops and expandable up to 127 loop devices (per loop) in mixed mode / loop powered and non-loop powered (system supports up to 762 digital loop addresses in total)
 
    -  esserbus PLus (Powered Loop) supplied, synchronously controlled, acoustic alarm signaling devices as per DIN EN 54 - 3 with alarm tone as per DIN 33404
 
    -  Up to 48 powered loop base sounders (series 9200) per loop
 
    -  Up to 32 powered loop IQ8Alarm per loop
 
    -  Up to 48 IQ8Quad with alarm device per loop
 
Additional Information:
The operating front must be ordered separately and is not included in the price. 
Scope of Delivery:
Housing with rear panel and front frame for operating panel fronts, neutral front, interface board, power supply module and system software.