Conventional Extinguishing Control Panel with touch screen

ESS-RP1r-Supra

The ESS-RP1r-Supra gas control panel has been designed to efficiently manage the automatic release sequence of any extinguishing system of gas, CO2 (according to EN12094:1/2003 requirements), foam, dust, aerosols or sprinklers.
The front panel includes a 4.3” colour touch screen which allows the user to move easily through the different events (alarm, fault, disabled) and visualize the real time event log and the input/outputs voltage levels.

• Compact extinguishing control panel with 32 bits microprocessor.
• Easy configuration from the keyboard and 4.3” TFT screen (480 x 272 pixels).
• 3 conventional zones: 2 for detectors and a third one which can be configured for detectors or call points.
• Inputs for abort and gas release call points and hold pushbutton.
• Release delay which can be configured from 0 to 60 sec. and verification time (before activating the sounders) from 0 to 10 min.
• Delays can be disabled from the keyboard (optional).
• Input circuits for flow and low pressure and open door monitoring.
• Two release circuits. The second one can be used independently for preactivation.
• Countdown timer display which indicates the seconds left for release.
• 44 status leds to quickly identify events.
• 7 relays for status indication and operating mode.
• Operating mode: Automatic, Manual and Disabled.
• Digital input for remote action such as: system reset, evacuation, silence or delay on/off.
• Plug-in terminals for all connections.
• Software for status visualization from the PC with remote connection option.
• Certified according to EN54-2/4:A2/2006 and EN12094/1:2003.